Related Auxiliary Bits/Words
Name
Online Edit Disable Bit
Validator
Online Edit Disable Bit
Online Editing Wait Flag

10-7-5 Turning OFF Outputs

Turn ON the Output OFF Bit (A500.15) to turn OFF the outputs of all Output Units regardless of the sta-
tus of the output bits in I/O memory. This can be used for urgent error processing when the Unit is oper-
ating in RUN or MONITOR mode. The INH indicator on the front of the CPU Unit will light yellow.
The status of the Output OFF Bit is maintained even if power is turned OFF and ON if there is a battery.
CPU Unit
I/O memory
Output OFF
Bit: ON
Additional Information
By default (i.e., if the IOM Hold Bit (A500.12) is turned OFF), all the outputs will be cleared (i.e.,
turned OFF) if the operating mode is switched from RUN or MONITOR mode to PROGRAM
mode. If an output bit in I/O memory is turned ON by the user program, the output will turn ON
when I/O is refreshed. To turn OFF all outputs from the Output Units regardless of the operating
mode, use the Output OFF Bit.
CJ2 CPU Unit Software User's Manual
Address
A527.00 to
Validates the Online Edit Disable Bit (A527.09).
A527.07
5A hex: Online Edit Disable Bit valid
Not 5A hex: Online Edit Disable Bit invalid
A527.09
To disable online editing, turn this bit ON and set the Online Edit Dis-
able Bit Validator (A527.00 to A527.07) to 5A.
A201.10
ON when an online editing process is on standby because online edit-
ing is disabled.
Output Unit
10 CPU Unit Functions
Description
All OFF
10
10-67