I/O Unit Refresh Times For Individual Units - Omron CJ2 - 02-2010 User Manual

Cj2 cpu unit software
Table of Contents

Advertisement

12-2-3 I/O Unit Refresh Times for Individual Units

Typical Basic I/O Unit Refresh Times
Name
8/16-point DC Input Units
32-point DC Input Units
64-point DC Input Units
8/16-point AC Input Units
16-point Interrupt Input Units
16-point Quick-response Input Units
8/16-point Relay Output Units
8-point Triac Output Units
8/16-point Transistor Output Units
32-point Transistor Output Units
64-point Transistor Output Units
24-VDC Input/Transistor Output Units
(16 inputs/16 outputs)
24-VDC Input/Transistor Output Units
(32 inputs/32 outputs)
TTL Input/TTL Output Units
(16 inputs/16 outputs)
B7A Interface Unit (64 inputs)
B7A Interface Unit (64 outputs)
B7A Interface Unit
(32 inputs/32 outputs)
Typical Special I/O Unit Refresh Times
Name
Analog Input Units
Analog Output
Units
Analog I/O Unit
Temperature Con-
trol Units
CJ2 CPU Unit Software User's Manual
CJ1W-ID201/211/212
CJ1W-ID231/232/233
CJ1W-ID261/262
CJ1W-IA201/111
CJ1W-INT01
CJ1W-IDP01
CJ1W-OC201/211
CJ1W-OA201
CJ1W-OD201/202/203/204/211/212/213
CJ1W-OD231/232/233/234
CJ1W-OD261/262/263
CJ1W-MD231/232/233
CJ1W-MD261/263
CJ1W-MD563
CJ1W-B7A14
CJ1W-B7A04
CJ1W-B7A22
Model
CJ1W-AD041/081(V1)
CJ1W-AD042
CJ1W-DA021/041/08V
CJ1W-DA042V
CJ1W-MAD42
CJ1W-TC@@@
12 CPU Unit Cycle Time
I/O refresh time per Unit
Model
0.0014 ms
0.0023 ms
0.0041 ms
0.0014 ms
0.0014 ms
0.0014 ms
0.0014 ms
0.0014 ms
0.0014 ms
0.0023 ms
0.0041 ms
0.0023 ms
0.0041 ms
0.0041 ms
0.0041 ms
0.0041 ms
0.0041 ms
I/O refresh time per Unit
CJ2H
0.05 ms
0.05 ms
0.05 ms
0.05 ms
0.05 ms
0.05 ms
CJ2H
CJ2M
0.0039 ms
0.0054 ms
0.0089 ms
0.0039 ms
0.0039 ms
0.0039 ms
0.0039 ms
0.0039 ms
0.0039 ms
0.0054 ms
0.0089 ms
0.0054 ms
0.0089 ms
0.0089 ms
0.0089 ms
0.0089 ms
0.0089 ms
CJ2M
0.07 ms
0.07 ms
0.07 ms
0.07 ms
0.07 ms
0.25 ms
12-7
12