CJ2 CPU Unit Software User's Manual
Code
Symbol/Operand
TIMU(541)/TIMUX(556) operates a decrementing timer with
TIMU (541)
units of 0.1-ms. The setting range for the set value (SV) is 0 to
N
0.9999 s for BCD and 0 to 6.5535 s for binary (decimal or
S
hexadecimal).
N: Timer number
Timer input
S: Set value
Timer PV
TIMUX(556)
N
Completion
Flag
S
N: Timer number
S: Set value
Timer Input Turned OFF before Completion
Flag Turns ON
Timer input
Timer PV
Completion
Flag
TMUH(544)/TMUHX(557) operates a decrementing timer with
TMUH(544)
units of 0.01-ms. The setting range for the set value (SV) is 0
N
to 0.09999 s for BCD and 0 to 0.65535 s for binary (decimal or
S
hexadecimal).
N: Timer number
Timer input
S: Set value
Timer PV
TMUHX(557)
N
Completion
Flag
S
N: Timer number
S: Set value
Timer Input Turned OFF before Completion
Flag Turns ON
Timer input
Timer PV
Completion
Flag
Timer
TTIM(087)/TTIMX(555) operates an incrementing timer
TTIM(087)
input
with units of 0.1-s. The setting range for the set value
N
(SV) is 0 to 999.9 s for BCD and 0 to 6,553.5 s for
S
binary (decimal or hexadecimal).
Reset
Timer input
input
N: Timer number
S: Set value
Timer PV
Timer
TTIMX(555)
input
N
S
Completion
Reset
Flag
input
Reset input
N: Timer number
S: Set value
Function
ON
OFF
SV
0
ON
OFF
ON
OFF
SV
0
ON
OFF
ON
OFF
SV
0
ON
OFF
ON
OFF
SV
0
ON
OFF
SV
Timing
resumes.
PV
maintained.
Appendices
Execution
Location
condition
Output
Required
Output
Required
Output
Required
A-11