Basic Setting Item - Panasonic FP7 User Manual

Multi input/output unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

5.1.1 Basic setting item

Setting item
Double word
error
annunciation
Warning
annunciation
Input voltage
mode
Input time
constant
Output terminal
polarity
(Note 1)
The parameters of the basic setup are set for the external terminal regardless of the selection contents
of functions.
Precautions when using FPWIN GR7 for configuration
When using the GR7 ver.2.12 or later on the Multi I/O Unit ver.1.0x, there are the following
restrictions.
● On the Multi I/O Unit ver.1.0x, the setting of the double word error annunciation specified by
the FPWIN GR7 is not reflected . It can be set using a program.Refer to
Warning".
● On the Multi I/O Unit Ver.1.0x, the following values specified for input time constants by the
FPWIN GR7 are set as 2 μs.
0.5 μs/1.5 μs/32 μs/64 μs/96 μs/128 μs/256 μs/8 ms
It can be set using a program.Refer to
WUME-FP7MXY-06
Default
Settings
Set whether or not to announce a double word access error
when it occurs.
Announce
Announce/Not announce
Set whether or not to announce a warning when it occurs.
Announce
Announce/Not announce
Select either the 5V-24V mode or 12V-24V mode.
The switching operation of the impedance of the input circuit,
5 V-24 V
minimum ON voltage and maximum ON voltage vary
according to the selected mode.
0 / 0.5μs / 1μs / 1.5μs / 2μs / 4μs / 8μs / 16μs / 32μs / 64μs /
2 μs
96μs / 128μs / 256μs / 2ms / 4ms / 8ms
The output circuit is switched. Select to match the actual
wiring.
Output OFF: Output OFF
Sink output: N channel output
Output Off
Source output: P channel output
N push-pull: Push-pull (negative logic)
P push-pull: Push-pull (positive logic)
"13.4.2 Input
setting".
5.1 Basic Setup
Related page
"P.12-4"
"P.12-7"
"P.3-3"
"P.3-3"
"P.3-5"
"13.4.1 Alarm/Error/
5-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp7mxy32dwdAfp7mxy32dwdh

Table of Contents