10.10 Positioning Control
● For the E-point control, input settings in one row.
● For P-point, C-point and J-point controls, they should be combined with E-point control of the
next step as a pair and the setting should be input in two rows.
● When E: End point is not selected in the next row after P: Pass point, C: Continuance point or
J: Speed point, the self-diagnostic error (error code 44: positioning error) is set to UM00066.
For details of positioning error codes, refer to
Occurs"".
Settings of J-point control
● For J-point control, select ""Increment"" as a control method.
● For changing speed during J-point control, set the target speed after the change in the
"Positioning Parameter" dialog box.

10.10.2 E-point Control (Single Speed Positioning)

● When the positioning table start contact or positioning simultaneous start contact turns on,
the pulse output starts and the positioning control operation is performed.