Omron sysmac EtherNet/IP NJ Series Connection Manual page 40

Machine automation controller
Hide thumbs Also See for sysmac EtherNet/IP NJ Series:
Table of Contents

Advertisement

3
Click the EtherNet/IP Device List
Tab.
4
Right-click Built-in EtherNet/IP Port
Settings - Port 2 and select Monitor
from the menu.
5
The Built-in EtherNet/IP Port
Settings - Port 2 Connection
Monitor Tab Page is displayed.
6
Click the Status Tab.
The tag data links are in normal
operation when the same check
boxes as in the figure on the right
are selected.
7
Click the Connection Status Tab.
Check that
is displayed to the
left of the applicable connection in
the Connection Name Column.
Check that 00:0000 is displayed in
the Status Column.
8
Click the Tag Status Tab.
Check that all the previously set
tags are displayed in the Tag Name
Column and that
the left of each tag name.
Check that "Normally resolved" is
displayed in the Status Column for
each tag.
is displayed to
7.EtherNet/IP Connection Procedure
Number: node number
Blue: connection normal
37