2-4 Correction at frosting and defrosting

When a decrease in heating capacity due to frosted and defrosting operations is considered, the value multi-
plied by the correction factor in the table below represents the heating capacity.
Correction factor table
Outdoor inlet air temp
(˚CWB)
Correction factor

2-5 Operation limit

• Cooling
30
25
20
15
10
-5
0
5
Outdoor temperature (˚CDB)
• Heating
30
25
20
15
10
-15
-10
-5
Outdoor temperature (˚CDB)
6
4
2
1.0
0.98
0.89
10
15
20
25
30
0
5
10
15
20
1 1 Outdoor units / Y series / PUMY-71·125VM
0
-2
-4
-6
0.88
0.89
0.9
0.95
35
40
45
50
9
-8
-10
0.95