Replacing The Gpu Board Or Gpu Lc Kit - Fujitsu PRIMERGY GX2560 M7 Upgrade And Maintenance Manual

Table of Contents

Advertisement

Concluding steps
"Installing the crossbar" on page
▶ Install all riser modules, see
"Installing the air duct" on page
"Reassembling" on page
"Connecting the power cord" on page
"Switching on the server" on page
When the system is powered on after a CPU has been replaced or
upgraded, the Global Error indicator will start flashing with the message
CPU has been changed.
This only indicates that the CPU configuration has been altered. There
is no technical problem.
Proceed as follows:
● Restart your server.
● As soon as the startup screen appears, press the [F2] function key to
enter the BIOS.
● If a password is assigned, enter the password and press [Enter].
● Select the Exit menu.
● Select Commit settings and Exit.
● Verify that the Global Error indicator stops flashing.
13.3

Replacing the GPU board or GPU LC kit

Field Replaceable Unit
(FRU)
Tools:
– Phillips PH2 / (+) No. 2 screwdriver
– Torx T15 screwdriver
GX2560 M7
68.
"Installing the riser module" on page
59.
49.
56.
58.
Upgrade and Maintenance Manual
Liquid cooling (LC)
Hardware: 30 minutes
64.
245