Horizontal Termination - Jøtul GF 370 DV II IPI Installation And Operation Instruction Manual

Direct vent gas stove
Hide thumbs Also See for GF 370 DV II IPI:
Table of Contents

Advertisement

139647_29 GF 370 DV II IPI 10/23

Horizontal Termination

Minimum vertical rise from the vent collar is a 24"
section vent pipe. See fig. 9. Minimum horizontal run
is 12" with natural gas and 18" with propane.
A maximum of two 90° or four 45° elbows may be
used in a horizontal termination. Whenever possible,
use 45° elbows instead a 90° elbow as they offer less
restriction to the flow of flue gases and intake air.
Reduce the overall horizontal run by 5 feet for each
additional elbow, whether 45° or 90°.
Snorkel Termination - ( 14" or 36"):
NATURAL GAS ONLY. DO NOT USE SNORKEL
TERMINATION WITH PROPANE FUEL.
A horizontal vent run may be made with a 90°
elbow directly to the rear of the stove only when
terminated by a 14 or 36 inch snorkel cap. Fig. 10
shows the minimum vent pipe requirements.
14" Snorkel: The maximum horizontal vent run
must not exceed a 24" section of pipe and must be a
minimum of 12".
36" Snorkel: The maximum horizontal vent run must
not exceed 5 feet and must be a minimum of 12".
The termination cap must not be recessed into
the wall or siding. Do not fill air space in wall around
termination cap with any type of insulation.
Wall Cut-out: A minimum 10" X 10" square hole
is adequate for proper pipe clearance through a
wall, provided the vent is positioned to maintain
2" minimum clearance at the top. A 1" minimum
clearance must be maintained to combustible
material around the other sides. See fig. 11.
Any horizontal run of vent must have a 1/4" rise for
every foot of run toward the termination cap.
All horizontal terminations must comply with the
clearance specifications to adjacent structures as
indicated in fig. 12.
Installation of a Vinyl Siding Standoff is required to
prevent damage to vinyl siding between the vent cap
and the exterior wall.
A horizontal termination cap must maintain a 3"
clearance to any overhead combustible projections that
are 2 1/2" or less. It must also maintain a 12" clearance
from projections that exceed 2 1/2". See fig. 13.
Vinyl siding projections require a default clearance of 18"
to the vent terminal.
A vent shall not terminate where it could cause
hazardous frost or ice accumulations on adjacent
property surfaces.
10
Figure 9. Minimum vent
pipe sections required for
horizontal termination:
A = 12" with NG
18" with LP
24”
74 1/2”
Figure 10. Minimum vent pipe
sections required for a 14"
Snorkel termination - Natural
Gas ONLY.
.
52”
Minimum Vent into
14” Snorkel Termination
Figure 11. Install a
listed wall thimble
according to manufac-
turer's instructions to
maintain required clear-
ance to combustible
materials.
A
Listed Wall
Thimble
14”
12”
Listed Wall
Thimble
NG
ONLY