Electrical installation
Installer reference guide
84
Capacity – Power
supply
6 kW 3N~ 400 V
9 kW 3N~ 400 V
3 Fix the cable with cable ties to the cable tie mountings.
During connection of the backup heater, miswiring is possible. To detect possible
miswiring, it is highly recommended to measure the resistance value of the heater
elements. Depending on the capacity and power supply, following resistance
values (see table below) should be measured. ALWAYS measure the resistance on
the contactor clamps K1M, K2M, and K5M.
K1M/1
K5M/13
K1M/3
K1M/5
K1M/3
K1M/5
K2M/1
K5M/13
K2M/3
K2M/5
K2M/3
K2M/5
K1M/5
K2M/1
Example measure resistance between K1M/1 and K5M/13:
Ω
Ω
F1B
F1B
L1 L2
L3
N
Q3DI
L1
L2
L3
N
3N~ , 50 Hz
400 V AC
3 kW
6 kW
1N~ 230 V
1N~ 230 V
52.9Ω
52.9Ω
∞
105.8Ω
∞
158.7Ω
26.5Ω
52.9Ω
∞
26.5Ω
∞
∞
∞
∞
52.9Ω
52.9Ω
∞
132.3Ω
K1M
K2M
K2M
1 3 5 13
1 3 5 13
2 4 6 14
2 4 6 14
K5M
1 3 5 13
2 4 6 14
X14M
X14M
1 2 3 4 5 6
6 kW
9 kW
3N~ 400 V
3N~ 400 V
∞
∞
105.8Ω
105.8Ω
105.8Ω
105.8Ω
105.8Ω
105.8Ω
∞
∞
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
∞
∞
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09