Sensors
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09
#
Code
[9.A.1]
[D‑08]
[9.A.2]
[D‑09]
External sensor
#
Code
[9.B.1]
[C–08]
Ext. amb. sensor offset
ONLY applicable in case an external outdoor ambient sensor is connected and
configured.
Description
Electricity meter 1:
0 None: NOT installed
1 1/10kWh: Installed
2 1/kWh: Installed
3 10/kWh: Installed
4 100/kWh: Installed
5 1000/kWh: Installed
Electricity meter 2:
0 None: NOT installed
1 1/10kWh: Installed
2 1/kWh: Installed
3 10/kWh: Installed
4 100/kWh: Installed
5 1000/kWh: Installed
In case of pulse meter for photovoltaic panels:
6 100/kWh for PV panel: Installed
7 1000/kWh for PV panel: Installed
Description
External sensor: When an optional external
ambient sensor is connected, the type of the
sensor must be set.
0 None : NOT installed. The thermistor in the
user interface and in the outdoor unit are used
for measurement.
1 Outdoor: Connected to the hydro PCB of the
outdoor
unit
measuring
temperature. Remark: For some functionality,
the temperature sensor in the outdoor unit is
still used.
2 Room: Connected to the hydro PCB of the
outdoor
unit
measuring
temperature. The temperature sensor in the
user interface is NOT used anymore. Remark:
This value has only meaning in room
thermostat control.
11
Configuration
|
the
outdoor
the
indoor
Installer reference guide
171