Daikin EWYA004D2V3P Installer's Reference Manual page 154

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWYA004D2V3P:
Table of Contents

Advertisement

11
|
Configuration
Installer reference guide
154
Value
5~8
Limitation when no actuators. When there is no heating output,
the pump speed limitation is applicable. When there is heating
output, the pump speed is only determined by delta T in
relation to the required capacity. With this limitation range,
delta T is possible and the comfort is guaranteed.
During sampling operation the pump runs for a short time to
measure the water temperatures, which indicate if operation is
required or not.
5: 90% pump speed during sampling
6: 80% pump speed during sampling
7: 70% pump speed during sampling
8: 60% pump speed during sampling
The maximum values depend on the unit type:
[9-0D]=0
a (kPa)
b (l/min)
[9-0D]=2/6
a (kPa)
[9-0D]=4/8
a (kPa)
a External static pressure
b Water flow rate
Description
[9-0D]=1/5
a (kPa)
[9-0D]=3/7
a (kPa)
b (l/min)
b (l/min)
b (l/min)
b (l/min)
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09