Daikin EWYA004D2V3P Installer's Reference Manual page 131

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWYA004D2V3P:
Table of Contents

Advertisement

EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09
If...
Space heating/cooling=On, and
The external room thermostat is
"Thermo OFF", and
Outdoor temperature drops below
6°C
Space heating/cooling=On, and
The external room thermostat is
"Thermo ON"
In case of 2 leaving water temperature zones:
If...
Space
heating/cooling=Off,
and
Outdoor ambient temperature drops
below 6°C
Space heating/cooling=On, and
Operation mode=Heating, and
The external room thermostat is
"Thermo OFF", and
Outdoor temperature drops below
6°C
Space heating/cooling=On, and
Operation mode=Cooling
Room thermostat control ([C‑07]=2)
During room thermostat control, room frost protection [2‑06] is guaranteed when
activated. If so, and the room temperature drops below the room antifrost
temperature [2‑05], the unit will supply leaving water to the heat emitters to heat
up the room again.
#
Code
[1.4.1]
[2-06]
[1.4.2]
[2-05]
INFORMATION
When the dedicated Human Comfort Interface (BRC1HHDA used as room
thermostat) is disconnected (because of incorrect wiring or damage of the cable),
then room frost protection is NOT guaranteed.
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
the temperature setpoint of the
leaving water will be lowered.
Room frost protection is guaranteed by
the normal logic.
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
the temperature setpoint of the
leaving water will be lowered.
The unit will supply leaving water to
the heat emitters to heat up the room
again, and
the temperature setpoint of the
leaving water will be lowered.
There is no room frost protection.
Description
Activation:
0 No: Antifrost functionality is OFF.
1 Yes: Antifrost functionality is on.
Room setpoint:
4°C~16°C
11
Configuration
|
Then...
Then...
Installer reference guide