Quiet
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09
Typical workflow
Using holiday mode typically consists of the following stages:
1
Activating the holiday mode.
2
Setting the starting date and ending date of your holiday.
To check if holiday mode is activated and/or running
If
is displayed on the home screen, holiday mode is active.
To configure the holiday
1 Activate the holiday mode.
▪
Go to [7.3.1]: User settings > Holiday > Activation.
7.3.1
Activation
From
Till
▪
Select On.
2 Set the first day of your holiday.
▪
Go to [7.3.2]: From.
▪
Select a date.
▪
Confirm the changes.
3 Set the last day of your holiday.
▪
Go to [7.3.3]: Till.
▪
Select a date.
▪
Confirm the changes.
About quiet mode
You can use quiet mode to decrease the sound of the outdoor unit. However, this
also decreases the heating/cooling capacity of the system. There are multiple quiet
mode levels.
The installer can:
▪
Completely deactivate quiet mode
▪
Manually activate a quiet mode level
▪
Enable the user to program a quiet mode schedule
If enabled by the installer, the user can program a quiet mode schedule.
INFORMATION
If the outdoor temperature is below zero, we recommend to NOT use the most quiet
level.
To check if quiet mode is active
If
is displayed on the home screen, quiet mode is active.
11
Configuration
|
—
—
—
Installer reference guide
157