Daikin EWYA004D2V3P Installer's Reference Manual page 233

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWYA004D2V3P:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Setting name
9.I
[C-07]
What is the unit control method in space operation?
9.I
[C-08]
Which type of external sensor is installed?
9.I
[C-09]
What is the required alarm output contact type?
9.I
[C-0A]
--
9.I
[C-0B]
--
9.I
[C-0C]
--
9.I
[C-0D]
--
9.I
[C-0E]
--
9.I
[D-00]
Which heaters are permitted if prefer. kWh rate PS is cut?
9.I
[D-01]
Contact type of preferential kWh rate PS installation?
9.I
[D-02]
Which type of DHW pump is installed?
9.I
[D-03]
Leaving water temperature compensation around 0°C.
9.I
[D-04]
Is a demand PCB connected?
9.I
[D-05]
Is the pump allowed to run if prefer. kWh rate PS is cut?
9.I
[D-07]
Is a solar kit connected?
9.I
[D-08]
Is an external kWh meter used for power measurement?
9.I
[D-09]
Is an external kWh meter used for power measurement, kWh
meter used for smart grid?
9.I
[D-0A]
--
9.I
[D-0B]
--
9.I
[D-0C]
--
9.I
[D-0D]
--
9.I
[D-0E]
--
9.I
[E-00]
Which type of unit is installed?
9.I
[E-01]
Which type of compressor is installed?
9.I
[E-02]
What is the indoor unit software type?
9.I
[E-03]
What is the number of backup heater steps?
9.I
[E-04]
Is the power saving function available on the outdoor unit?
9.I
[E-05]
Can the system prepare domestic hot water?
9.I
[E-06]
--
9.I
[E-07]
What kind of DHW tank is installed?
9.I
[E-08]
Power saving function for outdoor unit.
9.I
[E-09]
--
9.I
[E-0B]
Is a bi-zone kit installed?
9.I
[E-0C]
What bizone kit system type is installed?
9.I
[E-0D]
Is the system filled with glycol ?
9.I
[E-0E]
--
9.I
[F-00]
Pump operation allowed outside range.
9.I
[F-01]
Above which outdoor temperature is cooling allowed?
(*1) *EWYA_(*2) *EWAA
Range, step
Default value
R/W
0: Leaving water
1: External room thermostat
2: Room thermostat
R/W
0: No
1: Outdoor
2: Room
R/W
0: Abnormal
1: Normal
0
0
0
0
0
R/W
0: No
1: Only BSH
2: Only BUH
3: All
R/W
0: No
1: Open
2: Closed
3: Smart Grid
R/O
0: No DHW pump
1: Instant hot water
2: Disinfection
3: Circulation
4: Circulation and disinfection
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
R/W
0: No
1: Pwr consmp ctrl
R/W
0: No
1: Yes
R/O
0: No
1: Yes (DHW)
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
2
2
0
0
0
R/O
0~5
1: Minichiller
R/O
0
R/W (*1)
0: Reversible (*1)
R/O (*2)
1: Cooling only (*2)
R/W
0: No heater
1: External heater
R/O
0: No
1: Yes
R/O
0: No
1: Yes
0
R/O
0~8
0 OSO tank 150/180
1 FS with BUH
2 FS with BSH
3 OSO tank 200/250/300
4 Rotex without BSH (HYB)
5 Rotex with BSH
6 Third party tank for HYB
7 Third party tank, coil >= 1,05m2
8 Third party tank, coil >= 1,8m2
R/W
0: No
1: Yes
1
R/W
0: not installed
1: -
2: Bizone kit installed
R/W
0: Without hydraulic separator / no
direct pump
1: With hydraulic separator / no direct
pump
2: With hydraulic separator / with direct
pump
R/W
0: No
1: Yes
0
R/W
0: Restricted
1: Allowed
R/W
10~35°C, step: 1°C
20°C
Installer setting at variance with
default value
Date
Value
4P688017-1A - 2022.09