WARNING
Ethylene glycol is toxic.
WARNING
Due to the presence of glycol, corrosion of the system is possible. Uninhibited glycol
will turn acidic under the influence of oxygen. This process is accelerated by the
presence of copper and high temperatures. The acidic uninhibited glycol attacks
metal surfaces and forms galvanic corrosion cells that cause severe damage to the
system. Therefore it is important that:
the water treatment is correctly executed by a qualified water specialist,
a glycol with corrosion inhibitors is selected to counteract acids formed by the
oxidation of glycols,
no automotive glycol is used because their corrosion inhibitors have a limited
lifetime and contain silicates which can foul or plug the system,
galvanized pipes are NOT used in glycol systems since the presence may lead to
the precipitation of certain components in the glycol's corrosion inhibitor.
Electrical installation (see
DANGER: RISK OF ELECTROCUTION
WARNING
Electrical wiring connection method MUST be in accordance with the instructions
from:
This manual. See
The wiring diagram, which is delivered with the unit, located at the inside of the
service cover. For a translation of its legend, see
4
unit" [
 213].
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length into the unit.
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by
the safety devices required by the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, ALWAYS connect the backup heater
power supply and the earth cable.
WARNING
Stripped wire. Make sure that stripped wire cannot make contact with possible
water on the bottom plate.
"9 Electrical
installation" [
4
"9 Electrical
installation" [
4
 72])
 72].
"17.2 Wiring diagram: Outdoor
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09