Unit installation
Table 3: Maximum chimney length
When installing a chimney, the chimney length must be less than the maximum chimney length.
• Use the columns with the correct refrigerant charge. For intermediate refrigerant charges, use the columns with
the higher value. Example: If the refrigerant charge is 3.5 kg, use the columns of 4.05 kg.
• For intermediate diameters, use the column with the lower value. Example: If the diameter is 23 mm, use the
column of 22 mm.
• X: Not allowed
Maximum chimney length (m) – In case of Refrigerant charge=3.25 kg (and T=60°C)
Chimney
Straight pipe
1× 90° elbow
2× 90° elbow
3× 90° elbow
Table 4: Minimum bottom opening area for natural ventilation
Take the following into account:
• Use the correct table. For intermediate refrigerant charges, use the table with the higher value. Example: If the
refrigerant charge is 3.5 kg, use the table of 3.65 kg.
• For intermediate floor areas, use the column with the lower value. Example: If the floor area is 7.25 m², use the
column of 6.00 m².
• For intermediate release height values, use the row with the lower value. Example: If the release height is
1.90 m, use the row of 1.86 m.
• A
: Bottom opening area for natural ventilation.
nv
• A
: Minimum bottom opening area for natural ventilation.
nv-min
• (*): Already OK (no ventilation openings needed).
Release height (m)
1.66 m
1.86 m
2.06 m
2.26 m
2.46 m
2.66 m
2.86 m
3.06 m
Release height (m)
1.66 m
1.86 m
2.06 m
2.26 m
2.46 m
2.66 m
2.86 m
3.06 m
Release height (m)
1.66 m
1.86 m
2.06 m
2.26 m
2.46 m
2.66 m
Installer reference guide
62
Inside diameter of chimney (mm)
20 mm
22 mm
24.41 m
42.18 m
22.61 m
40.20 m
20.81 m
38.22 m
19.01 m
36.24 m
A
(dm²) – In case of Refrigerant charge=3.25 kg
nv-min
4.00 m²
6.00 m²
4.186 dm²
2.327 dm²
3.531 dm²
1.563 dm²
2.953 dm²
0.882 dm²
2.436 dm²
0.266 dm²
1.967 dm²
(*)
1.537 dm²
(*)
1.141 dm²
(*)
0.773 dm²
(*)
A
(dm²) – In case of Refrigerant charge=3.65 kg
nv-min
4.00 m²
6.00 m²
5.159 dm²
3.300 dm²
4.450 dm²
2.482 dm²
3.827 dm²
1.756 dm²
3.269 dm²
1.100 dm²
2.766 dm²
0.502 dm²
2.306 dm²
(*)
1.882 dm²
(*)
1.490 dm²
(*)
A
(dm²) – In case of Refrigerant charge=4.05 kg
nv-min
4.00 m²
6.00 m²
6.132 dm²
4.272 dm²
5.369 dm²
3.401 dm²
4.700 dm²
2.629 dm²
4.103 dm²
1.934 dm²
3.565 dm²
1.302 dm²
3.074 dm²
0.721 dm²
24 mm
26 mm
28 mm
67.50 m
102.40 m
149.26 m
65.34 m
100.06 m
146.74 m
63.18 m
97.72 m
144.22 m
61.02 m
95.38 m
141.70 m
Floor area of room A (m²) [! NOT room A + room B !]
8.00 m²
10.00 m²
1.474 dm²
0.689 dm²
0.600 dm²
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
Floor area of room A (m²) [! NOT room A + room B !]
8.00 m²
10.00 m²
2.513 dm²
1.788 dm²
1.581 dm²
0.751 dm²
0.749 dm²
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
Floor area of room A (m²) [! NOT room A + room B !]
8.00 m²
10.00 m²
3.551 dm²
2.886 dm²
2.562 dm²
1.789 dm²
1.681 dm²
0.809 dm²
0.886 dm²
(*)
0.160 dm²
(*)
(*)
(*)
In case of Refrigerant charge=4.05 kg (and T=60°C)
Inside diameter of chimney (mm)
20 mm
22 mm
24 mm
13.28 m
24.78 m
41.27 m
11.48 m
22.80 m
39.11 m
9.68 m
20.82 m
36.95 m
7.88 m
18.84 m
34.79 m
12.00 m²
14.00 m²
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
12.00 m²
14.00 m²
1.048 dm²
0.303 dm²
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
12.00 m²
14.00 m²
2.198 dm²
1.498 dm²
1.002 dm²
0.209 dm²
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
ERRA08~12E + ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05
26 mm
28 mm
64.11 m
94.87 m
61.77 m
92.35 m
59.43 m
89.83 m
57.09 m
87.31 m
16.00 m²
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
16.00 m²
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
16.00 m²
0.792 dm²
(*)
(*)
(*)
(*)
(*)