9
|
Electrical installation
In case of W1 models
Installer reference guide
116
3 (Optional) Power saving function: If you want to use the power saving
function:
▪ Disconnect X804A from X805A.
▪ Connect X804A to X806A.
INFORMATION
Power saving function. The power saving function is only applicable for V3 models.
For more information about the power saving function ([9.F] or overview field setting
[E‑08]), see
"Power saving
1 Power supply cable:
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block.
▪ Fix the cable with a cable tie.
Wires: 3N+GND
Maximum running current: Refer to name plate on unit.
4
function" [
 229].
ERRA08~12E + ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05