Daikin Altherma 3 R MT F Series Installer's Reference Manual page 302

Table of Contents

Advertisement

Field settings table
Breadcrumb Field code
Setting name
9.8.6
Allow electric heaters
9.8.7
Enable Room buffering
9.8.8
Limit setting kW
└─ Power consumption control
9.9.1
[4-08]
Power consumption control
9.9.2
[4-09]
Type
9.9.3
[5-05]
Limit
9.9.4
[5-05]
Limit 1
9.9.5
[5-06]
Limit 2
9.9.6
[5-07]
Limit 3
9.9.7
[5-08]
Limit 4
9.9.8
[5-09]
Limit
9.9.9
[5-09]
Limit 1
9.9.A
[5-0A]
Limit 2
9.9.B
[5-0B]
Limit 3
9.9.C
[5-0C]
Limit 4
9.9.D
[4-01]
Priority heater
9.9.F
[7-07]
BBR16 activation*
*BBR16 settings are only visible when the language of the user interface is set to
Swedish
└─ Energy metering
9.A.1
[D-08]
Electricity meter 1
9.A.2
[D-09]
Electricity meter 2
└─ Sensors
9.B.1
[C-08]
External sensor
9.B.2
[2-0B]
Ext. amb. sensor offset
9.B.3
[1-0A]
Averaging time
└─ Bivalent
9.C.1
[C-02]
Bivalent
9.C.2
[7-05]
Boiler efficiency
9.C.3
[C-03]
Temperature
9.C.4
[C-04]
Hysteresis
Installer settings
9.D
[C-09]
Alarm output
9.E
[3-00]
Auto restart
9.F
[E-08]
Power saving function
9.G
Disable protections
└─ Overview field settings
9.I
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
(*1) *6V*_(*2) *9W*_
(*3) Only applicable for models where cooling is possible
Range, step
Default value
R/W
0: No
1: Yes
R/W
0: No
1: Yes
R/W
0~20 kW, step: 0,5 kW
2 kW
R/W
0: No
1: Continuous
2: Inputs
3: Current Sensor
R/W
0: Amp
1: kW
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0: None
1: Booster Heater
2: Backup Heater
R/W
0: No
1: Yes
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
R/W
0: No
1: Outdoor
2: Room
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: No
1: 12 h
2: 24 h
3: 48 h
4: 72 h
R/W
0: No
1: Yes
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
-25~25°C, step: 1°C
0°C
R/W
2~10°C, step: 1°C
3°C
R/W
0: Abnormal
1: Normal
R/W
0: manual
1: automatic
R/W
0: No
1: Yes
R/W
0: No
1: Yes
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
25°C
7/12
Installer setting at variance with
default value
Date
Value
 4P717810‐1 ‐ 2022.11