To Connect The Electrical Wiring To The Outdoor Unit - Daikin Altherma 3 R MT F Series Installer's Reference Manual

Table of Contents

Advertisement

9
|
Electrical installation

9.2.2 To connect the electrical wiring to the outdoor unit

In case of V3 models
Installer reference guide
114
NOTICE
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
1 Open the service cover. See
2 Strip insulation (20 mm) from the wires.
a
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Insert the cables at the back of the unit, and route them through the factory-
mounted cable sleeves into the switch box.
a1+a2 Power supply cable (field supply)
b1+b2 Interconnection cable (field supply)
c1+c2 No use
d Cable sleeves (factory-mounted)
4 Inside the switch box, connect the wires to the appropriate terminals, and fix
the cables with cable ties. See:
"In case of V3
models" [
"In case of W1
models" [
1 Power supply cable:
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block.
▪ Fix the cable with a cable tie.
Wires: 1N+GND
Maximum running current: Refer to name plate on unit.
"7.2.2 To open the outdoor
b
4
 114]
4
 116]
4
unit" [
 65].
ERRA08~12E + ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05