PATTERN 3
START PATTERN 3
See table 3:
Is it possible to lead a chimney
outside the building respecting the maximum
chimney length?
3b
You CANNOT install the unit in the room. Place the unit in a larger
room.
Tables for PATTERN 1, 2 and 3
Table 1: Minimum floor area
For intermediate refrigerant charges, use the row with the higher value. Example: If the refrigerant charge is
3.5 kg, use the row of 3.65 kg.
Charge (kg)
3.25 kg
3.45 kg
3.65 kg
3.85 kg
4.05 kg
Table 2: Minimum release height
Take the following into account:
• For intermediate floor areas, use the column with the lower value. Example: If the floor area is 7.25 m², use the
column of 6.00 m².
• For intermediate refrigerant charges, use the row with the higher value. Example: If the refrigerant charge is
3.5 kg, use the row of 3.65 kg.
• (*): The release height of the unit without chimney (for 180 l units: 1.66 m; for 230 l units: 1.86 m) is already
higher than the minimum required release height. => OK (no chimney needed).
Charge (kg)
3.25 kg
3.45 kg
3.65 kg
3.85 kg
4.05 kg
ERRA08~12E + ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05
Yes
No
1.66 m (Unit=180 l)
11.73 m²
13.22 m²
14.80 m²
16.46 m²
18.22 m²
4.00 m²
6.00 m²
3.53 m
2.35 m
3.75 m
2.50 m
3.96 m
2.64 m
4.18 m
2.79 m
4.40 m
2.93 m
3a
You can install the unit in room A if you lead the chimney outside
the building.
A
Minimum floor area (m²)
Release height without chimney (m)
Minimum release height (m)
Floor area (m²)
8.00 m²
10.00 m²
2.01 m
1.80 m
2.14 m
1.91 m
2.26 m
2.02 m
2.38 m
2.13 m
2.51 m
2.24 m
7
Unit installation
|
1.86 m (Unit=230 l)
9.33 m²
10.52 m²
11.77 m²
13.10 m²
14.50 m²
12.00 m²
14.00 m²
(*)
(*)
1.74 m
(*)
1.84 m
1.71 m
1.95 m
1.80 m
2.05 m
1.89 m
Installer reference guide
16.00 m²
(*)
(*)
(*)
1.68 m
1.77 m
61