Configuration wizard: Tank ......... 32 Weather-dependent curve............33 Latest revisions of the supplied documentation may be available on 7.3.1 What is a weather-dependent curve? ......33 the regional Daikin website or via your dealer. 7.3.2 2-points curve ............. 33 Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B –...
▪ Do NOT pierce or burn. Daikin website (publicly accessible). ▪ Do NOT use means to accelerate the defrosting ▪ The full set of latest technical data is available on the Daikin process or to clean the equipment, other than those Business Portal (authentication required).
▪ Unpack the indoor unit completely according to the instructions unit and outdoor unit mentioned on the unpacking instructions sheet. Minimum refrigerant piping length between indoor 3 m unit and outdoor unit Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. NOTICE ▪ Pipework shall be protected from physical damage.
The room must be protected from frost. Installation with chimney connected to the outside. The release height is not relevant. There are no requirements to the minimum floor area. Not applicable Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Page 9
▪ Must be a permanent opening that cannot be closed. ▪ Must be ≥50% of A (minimum bottom opening area). nv-min Min. 50% ▪ Must be ≥1.5 m from the floor. of A nv-min (≥A nv-min EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Page 10
Ventilation openings must comply with A and with nv-min "Conditions ventilation openings" on previous page). Min. 50% Min. 50% ΔH1 of A of A nv-min nv-min (≥A (≥A nv-min nv-min Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Total refrigerant charge (kg) (dm²) nv-min 10.1 10.4 10.6 4× 10.9 11.1 11.3 3 If you have to do work behind the switch box, open the switch 11.5 box. 11.8 EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
4 Optional: If you want to fix the unit to the wall from inside the NOTICE unit: When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1 N•m. Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Connect both ends without brazing. If brazing should be needed, take the guidelines in the installer reference guide into account. ▪ Flare connections: Only use annealed material. ▪ Piping diameter: EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
When circulation in each space heating/cooling loop is controlled by remotely controlled valves, it is important that the minimum water volume is guaranteed, even if all of the valves are closed. Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
"6.3.7 To connect the space cooling/ output" [ 4 23]. operation control heating ON/OFF 5.4.3 To fill the domestic hot water tank See the installation manual of the domestic hot water tank. EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Page 18
[9.B.1]=1 (External sensor = mains to indoor unit) ▪ Addendum book optional Outdoor) equipment [9.B.2] Ext. amb. sensor offset Wires: 2+GND [9.B.3] Averaging time Maximum running current: 13 A [9.4] Booster heater Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
▪ Addendum book optional 1 2 3 equipment Wired room thermostat ▪ Installation manual of the wired room without multi-zoning base thermostat unit ▪ Addendum book optional equipment EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
The backup heater capacity can vary, depending on the indoor unit model. Make sure that the power supply is in accordance with the backup heater capacity, as listed in the table below. Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Page 21
Overcurrent fuse (field supply). Recommended fuse: 4‑pole; 20 A; curve 400 V; tripping class C. Safety contactor (in the switch box) Q1DI Earth leakage circuit breaker (field supply) Switch box Terminal (field supply) EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
3 Fix the cable with cable ties to the cable tie mountings. 6.3.5 To connect the domestic hot water pump Wires: (2+GND)×0.75 mm² DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A (continuous) Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
"4.2.1 To open the indoor 2 Connect the alarm output cable to the appropriate terminals as 1 Front panel shown in the illustration below. 2 Switch box cover 3 Switch box EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
1 Front panel 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Smart Grid relay kit (EKRELSG). The 2 incoming Smart Grid contacts can activate the following Smart Grid modes: Smart Grid contact Smart Grid operation mode Free running EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Page 26
×2 X5M.9 X5M.6 S11S X5M.5 ×4 X10M K1A, K2A Relays X10M Terminal block Screws for X10M Screws for K1A and K2A Sticker to put on the high voltage wires Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
The configuration influences the following: ▪ The calculations of the software ▪ What you can see on and do with the user interface You can configure the system via the user interface. EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Installer 5678 6 Press the left dial to confirm the new setting. 7 Press the center button to go back to the home screen. Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
▪ When Emergency is set to Automatic and a heat pump failure occurs, the backup heater automatically takes over the heat load, and the booster heater in the optional tank takes over the domestic hot water production. EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Page 30
NOTICE An overpressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations. Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
▪ 3: Relay 1 / Relay 2 Emergency Relay INFORMATION Settings [9.3.3] and [9.3.5] are linked. Changing one setting influences the other. If you change one, check if the other is still as expected. EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Influence of the LWT setpoint mode [2.4] is as follows: ▪ In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving water temperatures, either preset or custom. Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
▪ during storage comfort, to prioritize the domestic hot water preparation. When the tank temperature rises above this value, domestic hot water preparation and space heating/cooling are executed sequentially. Code Description [5.4] [6-0C] Reheat setpoint: ▪ 30°C~min(50,[6‑0E])°C EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
[2.4] Main zone > Setpoint WD heating, fixed cooling mode OR Weather dependent Main zone – Cooling [2.4] Main zone > Setpoint Weather dependent mode Additional zone – Heating Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
To fine-tune the weather-dependent curve: 2-points curve Code Description The following table describes how to fine-tune the weather- [8.3] Number that users can call in case of dependent curve of a zone or tank: problems. EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Solar kit settings are shown but are NOT applicable for this Depending on the selected installer settings and unit type, unit. Settings shall NOT be used or changed. settings will be visible/invisible. Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Next commissioning instructions in this chapter, a general ▪ Between the local supply panel and the indoor unit commissioning checklist is also available on the Daikin ▪ Between the indoor unit and the valves (if applicable) Business Portal (authentication required).
1 Set the user permission level to Installer. See "To — ▪ C/H signal test level" [ 4 28]. change the user permission ▪ DHW pump test 2 Go to [A.1]: Commissioning > Operation test run. Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
10 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 10.1 Piping diagram: Indoor unit...
Page 42
For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Installation manual EBBH/X11+16DF Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Page 43
Only for Human Comfort Interface 2 core A8P: X801M: 3-5 2×0.75 signal X5M: 11-12 A14P: P1-P2 user interface 2 core Power limitation demand input 4 communication A8P: X801M: 4-5 signal 4D134576 EBBH/X11+16DF Installation manual Daikin Altherma 3 R W 4P643600-1B – 2021.10...
Page 44