Daikin Altherma 3 R MT F Series Installer's Reference Manual page 242

Table of Contents

Advertisement

12
|
Commissioning
Installer reference guide
242
Status
Main zone (mixed)
Pump additional
OFF
zone
Example: Air purge on main zone:
b
a
d
Example: Air purge on additional zone:
b
a
d
a Outdoor unit
b Indoor unit
c Backup heater
d Plate heat exchanger
e DHW tank
M1S 3-way valve (mixing valve for the main/mixed zone)
M3S 3-way valve (space heating/domestic hot water)
To perform a manual air purge
INFORMATION
When purging the main zone, make sure the setpoint for the main zone is at least
5°C higher than the actual water temperature inside the unit.
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Space heating/cooling and Tank operation.
1 Set the user permission level to Installer. See
the user permission
2 Go to [A.3]: Commissioning > Air purge.
3 In the menu, set Type = Manual.
Air purge on zone ...
Additional zone
(direct)
ON
e
M1S
c
45°C
M3S
e
M1S
c
45°C
M3S
4
level" [
 143].
Tank (domestic hot
water)
ON
45°C
35°C
45°C
35°C
"To change
ERRA08~12E + ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05