Installation Site Requirements Of The Outdoor Unit - Daikin Altherma 3 R MT F Series Installer's Reference Manual

Table of Contents

Advertisement

7
|
Unit installation

7.1.1 Installation site requirements of the outdoor unit

Installer reference guide
52
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
WARNING
DO NOT reuse refrigerant piping that has been used with any other refrigerant.
Replace the refrigerant pipes or clean thoroughly.
INFORMATION
Also read the following requirements:
"2 General safety
"7.1.3 Installation site requirements of the indoor
length and height difference).
Mind the spacing guidelines. See
NOTICE
Do NOT stack the units on each other.
Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit's air outlet causes short
circuit (suction of discharge air). This may result in:
deterioration of the operational capacity;
frequent frost acceleration in heating operation;
disruption of operation due to decrease of low pressure or increase of high
pressure;
a broken fan (if a strong wind blows continuously on the fan, it may start rotating
very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing the wall and
NOT directly exposed to the wind.
b
a Baffle plate
b Prevailing wind direction
c Air outlet
Do NOT install the unit in the following places:
4
precautions" [
 10].
"17.1 Service space: Outdoor
b
a
4
unit" [
 54] (refrigerant piping
4
unit" [
 279].
ERRA08~12E + ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05

Advertisement

Table of Contents
loading

Table of Contents