Controller Resetting (Following System Shutdown Or Warning) - Kohler KG40 Operation

Industrial generator set
Table of Contents

Advertisement

2.4.8

Controller Resetting (Following System Shutdown or Warning)

Use the following procedure to restart the generator set after a system shutdown or to clear a warning lamp condition. This
procedure includes the resetting of the optional remote annunciator.
Refer to the section titled: Emergency Stop Switch Reset Procedure, to reset the generator set after an emergency stop.
1.
Disconnect the generator set load using the line circuit breaker or automatic transfer switch.
2.
Correct the cause of the fault shutdown or warning. See the Safety Precautions and Instructions section of this manual
before proceeding.
3.
Start the generator set by pressing the generator set master control OFF/RESET button and then press the RUN button.
When equipped, the remote annunciator alarm horn sounds. Press the ALARM SILENCE/LAMP TEST button to stop
the alarm horn. The lamp turns off.
4.
Test operate the generator set to verify correction of the shutdown cause.
5.
Press the generator set master control OFF/RESET button to stop the generator set.
6.
Press the generator set master control AUTO button.
7.
Reconnect the generator set load via the line circuit breaker or automatic transfer switch.