Kohler KG40 Operation page 39

Industrial generator set
Table of Contents

Advertisement

Description
Charger Depleted Battery
Voltage Target
Charger Equalize Stage
Duration (Min)
Note:
Equalize is only available with
FLA/VRLA topology selected.
Charger Manual Equalize
Cycle Activation
Note:
Equalize is only available with
FLA/VRLA topology selected.
Charger Maximum Absorption
Time Threshold (Min.)
Charger Maximum Bulk Time
Threshold (Min)
Charger Refresh Charge
Cycle Time (Hr)
Charger Return To Bulk State
Voltage Threshold (V)
Charger Starter Battery
Topology
Note:
Verify that the battery topology
is set correctly for the battery
type that is used.
Incorrect charger output
system voltage may cause
irreversible damage to the
battery and abnormal out
gassing.
Charger System Battery
Voltage
Note:
Verify that the system
voltage is set correctly for
the battery type that is used.
Incorrect charger output
system voltage may cause
irreversible damage to the
battery and abnormal out
gassing.
Charger Temperature
Compensation Enable
Charger Temperature
Compensation Slope (mV/ C)
*
Function requires optional input sensors or is engine ECM dependent on some generator set models.
† ECM inputs are engine-manufacturer dependent.
‡ Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST- Short Term, LT- Long Term
TP-6694
6/22
Fault
Controller
Lamp
Display
Alarm
Warning
Message
Horn
Shutdown
GenSet
Write
Mode
Access
Always
Display
Running
Range
SiteTech
Stopped
Setting
4–12
(12 V)
S
18–24
(24 V)
S
A
60–480
Active
S
A
Inactive
60–360
60–600
S
A
(NiCad
only)
S
A
6–600
0,
S
A
23–672
10–13
(12 V)**
S
A
20–26
(24 V)**
Default
FLA/
VRLA
S
A
AGM
Gel
NiCad
System
12 VDC
S
A
System
24 VDC
Active
S
A
Inactive
-40–0
(12 V)
S
A
-80–0
(24 V)
Time
Default
Delay
Time
Default
Range
Delay
Selection
(sec.)
(sec.)
10
(12 V)
20
(24 V)
Inactive
240
480
335
12.8
(12 V)
25.6
(24 V)
Default
12 VDC
Inactive
-30
(12 V)
- 60
(24 V)
39