Starting - Kohler KG40 Operation

Industrial generator set
Table of Contents

Advertisement

2.4.1

Starting

Local Starting
Press the master control RUN button to start the generator set at the controller.
Note:
The alarm horn sounds and the Not-In-Auto Warning display appears whenever the generator set master control button is not
in the AUTO mode.
Button
Generator
Mode
Set Status
Off
On (or
Cranking)
AUTO
Running and
then Off
OFF/RESET
Off
Off (or
Cranking)
RUN
(unit fails to
start)
Off
Off (or
Cranking)
RUN
On
(unit starts)
Running and
then Off
* Alarm silence only works when in the Auto mode unless the Always selection is made using SiteTech™.
Refer to the section titled: GenSet System for more information
Figure 10
Master Control Button Function Summary
Note:
The transient start/stop function of the controller prevents accidental cranking of the rotating engine. The generator set stops
and recranks when the OFF/RESET button is momentarily pressed and then the RUN button is pressed.
Auto Starting
Press the master control AUTO button to allow startup by the automatic transfer switch or remote start/stop switch (connected
to controller terminals 3 and 4).
Terminals 3 and 4 connect to a circuit that automatically starts the generator set crank cycle when an external source closes the
circuit.
Note:
The controller provides up to 30 seconds of programmable cyclic cranking and up to 60 seconds rest with up to 6 cycles. The
default setting is 15 seconds cranking and 15 seconds rest for 3 cycles. Make cyclic cranking adjustments using SiteTech™
software.
Prime Power Switch
The controller has an optional prime power mode of operation. The prime power mode requires installation of an optional prime
power switch kit. See the section titled: Accessories, for instructions on how to install the optional prime power switch kit. The
prime power switch kit prevents engine starting battery drain when the generator set is shut down and no external battery
charging is available.
Move the prime power switch located on the junction box to the CONTROLLER ON position before attempting to start the
generator set. When the prime power mode is off, all controller functions including the digital display, LEDs, and alarm horn are
operative.
Stop the generator set using the stopping procedures in the section titled: Stopping (User Stopping and Fault Shutdown) before
placing the generator set in the prime power mode. Move the prime power switch located on the junction box to the
CONTROLLER OFF position. When the generator set is the prime power mode, all controller functions including the digital
display, LEDs, alarm horn, and communications are inoperative.
TP-6694
6/22
Button Lamp
Fault Lamp
Green
Red
Red
Yellow
Yellow
Yellow
Red
Yellow
Yellow
Yellow
Red
Alarm
Alarm Silence
Horn
Button *
Off
Off
On
Off
Pressed
On
Off
Pressed
On
Off
Pressed
On
Off
Pressed
On
Off
Pressed
On
Off
Pressed
Alarm Silence
Lamp
Controller Display
Scrolling Overview
Menu Only
Shutdown Message
Yellow
Not in Auto Warning
Yellow
Not in Auto Warning
Yellow
Locked Rotor
Shutdown (or other
Yellow
shutdown message)
Not in Auto
Warming
Yellow
Shutdown Message
Yellow
45