Kohler KG40 Operation page 152

Industrial generator set
Table of Contents

Advertisement

TB3 Terminal Strip
Accessory Power Output Connections
Terminal
Description
TB3-1
E-Stop
TB3-1A
E-Stop
TB3-3
Remote Start
TB3-4
Remote Start
TB3-AUX
Auxiliary
TB3-AUXR
Auxiliary-R
P1 24-Pin Connector
Engine Wiring Harness
Terminal
Description
P1-12
14P+12VDC
P21 6-Pin Connector
RS-485 (RSA II)
Terminal
Description
P21-1
GND
P21-2
(+)
P21-3
(- )
P21-4
GND
P21-5
(+)
P21-6
(- )
TB1 Terminal Strip Designations
Analog and Digital Input Connections
Terminals
Controller
on Board
Designation
TB1-DI 1
DIn A1
TB1-DI 2
DIn A2
TB1-DI 3
DIn A3
TB1-AI 1
AIn A1
TB1-AI 2
AIn A2
TB1-GND
Figure 91
Controller Connections
Note:
When battery charger GM87448 is used, the Battery Charger Fault is communicated through CAN communication and the
connection on TB1 is not used. Also, this connection is factory reserved for Enclosure Temperature: High Shutdown on select
Telecom units.
P25 Connector
RJ45 Remote I/O In
Connects to controller P23
P25 Connector
RJ45 Remote I/O In
Connects to controller P23
P27 Connector
CAN Terminator
Place the P27 jumper on the IN pins
152
Connection
E- Stop Ground
E- Stop
Remote Start
Remote Start
Aux. Shutdown Sw.
Aux. Shutdown Sw.
Connection
Prime Power Switch
Connection
Shield
Red
Black
Shield
Red
Black
SiteTech
Designation
A1
A2
A3
A1
TP-6694
6/22

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kg150Kg100Kg180Kg5025ccl36ccl