Low Fuel (Level/Pressure) Switch - Kohler KG40 Operation

Industrial generator set
Table of Contents

Advertisement

6.1.8

Low Fuel (Level/Pressure) Switch

Some gaseous-fueled models offer a low fuel pressure switch. The low fuel pressure switch connects to the same controller
terminal as the low fuel level switch on diesel-fueled models. See Figure 76, Figure 77, and Figure 78.
Note:
The main tank or the transfer/day tank includes the low fuel level switch. The fuel tank supplier typically provides the low fuel
level switch.
Figure 76
Low Fuel Switch (Level or Pressure)
Figure 77
Low Fuel Switch Connection to Controller Connection
Switch Rating
Wiring Recommendation
Gauge
18-20
14
10
Figure 78
Switch Rating & Wiring Recommendation
142
Low Fuel Switch (Optional)
Provided by Fuel Tank Supplier
Connect to TB1 (for
warning) or TB3
(for shutdown)
APM402 / DEC 3000 Controller
Aux Warning Switch
(Customer Provided)
12 volts DC minimum, 0.5 amp minimum
mm (ft.)
30.5 (100)
153 (500)
305 (1000)
Located in Main Tank as
Battery Ground
Aux Shutdown Switch
(Customer Provided)
TP-6694
6/22