Kohler KG40 Operation page 153

Industrial generator set
Table of Contents

Advertisement

P28 Connector
Single-Ended (0-5 V) Analog Input Connections
Terminal
Description
P28-GND
AGND Analog Return
P28-VN1
NO Connection
P28-VP1
ACH1 Signal
P28-+5V
Supply (.05 amp max.)
P28-GND
AGND Analog Return
P28-VN2
NO Connection
P28-VP2
ACH2 Signal
P28-+5V
Supply (0.05 amp max.)
P28 Connector
Differential (+/- 3 V) Analog Input Connections
Terminal
Description
P28-GND
AGND Analog Reference
P28-VN1
ACH1 Negative Differential Signal
P28-VP1
ACH1 Positive Differential Signal
P28- +5V
Supply (.05 amp max.)
P28-GND
AGND Analog Reference
P28-VN2
ACH2 Negative Differential Signal
P28-VP2
ACH2 Positive Differential Signal
P28- +5V
Supply (0.05 amp max.)
P29 Connector
2 Amp. K1 Relay Output (2.1) Connections
Terminal
Description
P29-NC
Normally Closed
P29-COM
Common
P29-NO
Normally Open
P30 Connector
2 Amp. K2 Relay Output (2.2) Connections
Terminal
Description
P30-NC
Normally Closed
P30-COM
Common
P30-NO
Normally Open
P31 Connector
2 Amp. K3 Relay Output (2.3) Connections
Terminal
Description
P31-NC
Normally Closed
P31-COM
Common
P31-NO
Normally Open
P32 Connector
10 Amp. K4 Relay Output (2.4) Connections
Terminal
Description
P32-NC
Normally Closed
P32-COM
Common
P32-NO
Normally Open
10 Amp. K5 Relay Output (2.5) Connections
Terminal
Description
P32-NC
Normally Closed
P32-COM
Common
P32-NO
Normally Open