180-500 RZXB/REZXB/REZXC/RZXD/REZXD (PSI/ Doosan 11.1L, 14.6L, 18.3L, and 21.9L Engines)
LPG Vapor or Liquid Withdrawal with Single Fuel Valve
See Figure 46.
Disconnect lead 70E.
Disconnect lead N6.
Disconnect lead N11 (250 – 500 kW).
Disconnect lead 73A (180 – 200 kW).
Disconnect lead 73A and 73A1 (250 – 500 kW).
Disconnect lead 65A.
Connect lead 70B2 to fuel valve 1 (FV1), red/black wire.
For 250 – 500 kW (14.6 L – 22 L engines), connect lead 70B2 to fuel valve 1A (FV1A) and lead 70B2A to fuel
o
valve 1B (FV1B), red/black wires.
Connect lead 73B to fuel valve 1 (FV1), red/white wire.
For 250 – 500 kW (14.6 L – 22 L engines), connect lead 73B to fuel valve 1A (FV1A) and 73B1 to fuel valve 1B
o
(FV1B), red/white wire.
Connect lead N7 to fuel valve 1 (FV1), green wire.
For 250 – 500 kW (14.6 L – 22 L engines), connect lead N7 to fuel valve 1A (FV1A) and lead N10 to fuel valve
o
1B (FV1B), green wires.
Connect lead 63 to normally closed (NC), low fuel pressure sensor 1.
Connect lead N3 to common (COM), low fuel pressure sensor 1.
Connect lead 65 to lead N5 (ground).