Table 3: Ul 864 Programming Requirements - Bosch D9412GV3 Program Entry Manual

Table of Contents

Advertisement

D9412GV3/D7412GV3 | Program Entry Guide | 1.0
1.3
Guide to UL 864 Programming Requirements
This section identifies the programming requirements you must make in order to comply with UL 864
Commercial Fire applications.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
you must limit certain programming features or options to specific values. Refer to Table 3.

Table 3: UL 864 Programming Requirements

Product Feature/Option
If using two phone lines:
Phone 1 through 4
Phone Supervision
Alarm On Fail
Buzz On Fail
Two Phone Lines
Expand Test Report
Fire Reports
R# Fire Supervisory
Missing
Test Reports
AC Fail Report
AC Restoral Report
Battery Missing Report
Low Battery Report
Battery Restoral Report
R# Service Start Report
R# Service End Report
R# Fire Walk St Report
R# Fire Walk End Report
R# Walk Test St Report
R# Walk Test End Report
AC Fail Time
AC Fail Display
AC Tag Along
AC/Battery Buzz
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Introduction
Permitted in
Possible Settings
UL 864? (Y/N)
Yes
24 characters
Yes
0 to 240 sec
No
Yes / No
Yes
Yes / No
Yes
Yes / No
Yes
Yes/No
Yes
Yes / No
Required
Yes/No
Yes
Yes / No
Yes
Yes / No
Yes
Yes / No
Yes
Yes / No
Yes
Yes / No
Yes
Yes / No
Required
Yes / No
Required
Yes / No
Required
Yes / No
Required
Yes / No
Required
Yes / No
Required
Yes / No
Yes
1:00 to 90:00 min
Yes
10 to 300 sec
Yes
Yes / No
Yes
Yes / No
Get other manuals https://www.bkmanuals.com
Settings Permitted in
UL 864
Program a valid phone
number
10 to 200 sec
Set to No
Set to Yes
Set to Yes when using
PSTN communications.
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Enter 1:00
10 to 200 sec
Set to Yes
Set to Yes
EN | 9
Refer to
Page:
12
16
16
16
16
17
21
21 (Table 9)
22
23 (Table 13)
23 (Table 13)
23 (Table 13)
23 (Table 13)
23 (Table 13)
26 (Table 17)
26 (Table 17)
26 (Table 17)
26 (Table 17)
26 (Table 17)
26 (Table 17)
29
29
29
30

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv3

Table of Contents