Miscellaneous; Area Parameters - Bosch D9412GV3 Program Entry Manual

Table of Contents

Advertisement

D9412GV3/D7412GV3 | Program Entry Guide | 2.0
2.7

Miscellaneous

Duress Type
Default:
0
Selection:
0, 1, 2, or 3
0
Do not send a duress event with any
passcode.
1
Increase the last digit by 1 to generate an
alarm. For example, if the passcode is 6123,
6124 activates a duress alarm.
If the last digit of the passcode is 0, a duress
alarm occurs when the user enters 1 as the
last digit of the passcode.
If the last digit of the passcode is 9, a duress
alarm occurs when the user enters 0 as the
last digit of the passcode.
2
Increase the last digit by 2 to generate an
alarm. For example, if the passcode is 6123,
6125 activates a duress alarm.
If the last digit of the passcode is 8, a duress
alarm occurs when the user enters 0 as the
last digit of the passcode.
If the last digit of the passcode is 9, a duress
alarm occurs when the user enters 1 as the
last digit of the passcode.
3
Send a Duress event when any Passcode with
L# Send Duress set to Yes is entered.
This program item determines when a passcode
entry with L# Send Duress authority should produce
a duress alarm.
Duress is enabled in Area Parameters by
setting A# Duress Enable to Yes.
The duress alarm activates when a user
enters the duress passcode followed by
the termination keys ([ESC] or [ENT]).
For SIA CP-01 Compliance
Duress Type must be set to 3.
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Panel and Area Wide Parameters
Cancel Report
Default:
Selection:
Yes
No
A Cancel and Fire Cancel Report is created when a
passcode is entered to silence an Alarm Bell or a Fire
Bell before the bell time expires.
For SIA CP-01 Compliance
This prompt must be set to Yes.
Call for Service Text
Default:
Selection:
Enter the text to display on a D1260 series keypad
when the control panel is out of service.
2.8
This programming module contains three
programming categories: Area Parameters, Bell
Parameters, and Open/Close Options.
2.8.1
Enter the area number you are programming.
Area# Area On
Default:
Selection:
Yes
No
Use this program item to enable or disable the area
specified.
Refer to Keypad Programming of Area # On and
Area# Account Number on page 37.
Get other manuals https://www.bkmanuals.com
No
Yes or No
Send Cancel and Fire Cancel
Reports according to routing.
Do not send Cancel and Fire Cancel
Reports.
Refer to the program record sheet
Twenty alphanumeric characters

Area Parameters

Area Parameters
Yes (Area 1 only)
Yes or No
Enable area.
Disable area.
EN | 36