5.0 AUXPARM

5.1

Introduction

The programming prompts in this section are
primarily used for programming enhanced
communication capabilities for the GV3 Series
Control Panels.
Enhanced communications is the ability to provide
communication functions for the control panels over
SDI. These communication methods include:
Routing control panel events through a network
interface module (NIM). A network interface
module (NIM) can be a DX4020 or an ITS-
DX4020-G.
Communicating with remote programming
software (RPS) using a (NIM).
Communicating with a remote or local automation
software package.
5.2

RPS Requirements

The AUXPARM section currently has seven sections:

SDI Automation

SDI RPS Parameters
Enhanced Communications
SDI RPS/Enhanced Communication
Configuration
Miscellaneous
Cross Point Parameters
Route Group Rate
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
AUXPARM
5.3
SDI automation defines the characteristics of a serial
interface module (SIM) when used with home or
business automation software. The SIM is a two-way
SDI to a serial communication module that allows the
control panels to send and receive information to and
from an external software program.
This automation protocol allows external software
programs to interact and perform functions such as:
arming and disarming areas,
changing user passcodes and names, and
turning relays on and off.
The items described in this section allow some
simple configuration options. To receive the SIM
automation protocol; however, you must contact
Bosch Security Systems, Inc. Technical Support at
(888) 886-6189.
Enable SDI Auto
Default:
Selection:
Yes
No
Changing this item to Yes enables the automation
address (SDI Address 80).
Supervise SDI 80
Default:
Selection:
Yes
No
This item determines whether the serial interface
module (SIM) is supervised or not. If the SIM is
supervised, disconnecting the SIM from the control
panel creates a Trouble SDI 80 Event and the
keypad annunciates a trouble tone (if programmed)
and displays SERVC SDI 80.
Get other manuals https://www.bkmanuals.com
SDI Automation
The SIM can be a D9133, DX4010i, or
DX4020 (configured to emulate serial
communication).
A DX4010i can be used only for
programming.
No
Yes or No
Enable Automation software.
Disable Automation software.
No
Yes or No
Supervise the serial interface
module (SIM).
Do not supervise the serial interface
module (SIM).
Trouble SDI 80 Reports are always sent
using the account number for Area 1.
EN | 125