Table 14. Supported video resolution options  (continued)
Resolution
1920 x 1080
1920 x 1200

Environmental specifications

Table 15. Continuous Operation Specifications for ASHRAE A3 
Continuous Operation Specifications for ASHRAE A3
Temperature range for altitudes <= 900 m (<= 2953 ft)
Humidity percent range (non-condensing at all times)
Operational altitude de-rating
Table 16. Continuous Operation Specifications for ASHRAE A4 
Continuous Operation Specifications for ASHRAE A3
Temperature range for altitudes <= 900 m (<= 2953 ft)
Humidity percent range (non-condensing at all times)
Operational altitude de-rating
Table 17. Common Environmental Specifications for ASHRAE A3 and A4 
Continuous Operation Specifications for ASHRAE A3
Maximum temperature gradient (applies to both operation and
non-operation)
Non-operational temperature limits
Non-operational humidity limits
Maximum non-operational altitude
Maximum operational altitude

Thermal air restrictions

Thermal air restrictions
ASHRAE A3/A4 configuration restriction
● NVMe SSD and EDSFF are not supported
● A2 GPU is not supported
Refresh rate (Hz)
60
60
Color depth (bits)
8, 16, 32
8, 16, 32
5 — 40°C (41-104°F) with no direct sunlight on the
equipment
8% RH with -12°C minimum dew point to 85% RH with 24°C
(75.2°F) maximum dew point
Maximum temperature is reduced by 1°C/175 m (33.8°F/574
Ft) above 900 m (2953 Ft)
5 — 40°C (41-104°F) with no direct sunlight on the
equipment
8% RH with -12°C minimum dew point to 90% RH with 24°C
(75.2°F) maximum dew point
Maximum temperature is reduced by 1°C/175 m (33.8°F/574
Ft) above 900 m (2953 Ft)
20°C in an hour* (36°F in an hour) and 5°C in 15 minutes
(41°F in 15 minutes), 5°C in an hour* (41°F in an hour) for
tape
NOTE:
Per ASHRAE thermal guidelines for tape hardware,
these are not instantaneous rates of temperature change.
-40 to 65°C (-104 to 149°F)
5% to 95% RH with 27°C (80.6°F) maximum dew point
12,000 meters (39,370 feet)
3,048 meters (10,000 feet)