NOTE
• When the Pr.307 setting value is equal to or larger than the Pr.308 setting value, the output value for terminal AM1 will
always be zero.
Pr.290 = "0, 1, 4, or 5" (without negative output)
Analog output
Limited at 10 V
10 V
-100%
0
Analog output value
Analog output value
when output signal
when output signal
is at maximum (Pr.308)
is zero (Pr.307)
NOTE
• When the Pr.307 setting value is equal to the Pr.308 setting value, the output value for terminal AM1 will always be the
parameter setting value.
Pr.309 = "10 or 11"
Pr.290 = "8, 9, 12, or 13" (with negative output)
Limited at 10 V
Analog output value
when output signal
is zero (Pr.307)
-100%
Output signal
100%
value
Limited at -10 V
Analog output
10 V
0
Analog output value
when output signal
is at maximum (Pr.308)
-10V
CONTROL CIRCUIT OUTPUT SIGNAL
Limited at 10 V
4
Output signal
100%
value
75