Mitsubishi Electric FR-E8AXY E KIT Instruction Manual page 75

Table of Contents

Advertisement

 Setting output signals
Set the output signals to be monitored. Negative values can be used for indication via terminal AM1 (output range: -10 to +10
VDC). The setting of Pr.306 is the same as that of Pr.158 AM terminal function selection. For details of Pr.158, refer to the
FR-E800 Instruction Manual (Function).
 Adjusting the analog signal (Pr.307, Pr.308)
Use Pr.307 to set the value for zero analog output (meter zero) and Pr.308 for maximum analog output (full scale). (Refer to
page
72.)
Pr.290 = "0, 1, 4, or 5" (without negative output)
Analog output
10 V
-100%
0
74
CONTROL CIRCUIT OUTPUT SIGNAL
Pr.309 = "0 or 1"
Output signal value
when analog output
is at maximum (Pr.308)
Output signal
100%
value
Output signal value
when analog output
is zero (Pr.307)
Pr.290 = "8, 9, 12, or 13" (with negative output)
Analog output
10 V
Output signal value
when analog output
is zero (Pr.307)
-100%
0
-10V
Output signal value
when analog output is
at maximum (Pr.308)
Output signal
100%
value