3.2.8

Torque setting voltage bias and gain

The magnitude (slope) of the torque can be set as desired in relation to the torque setting signal (0 to 5 VDC or 0 to 10 VDC).
Pr.
Name
C16
(919)
Terminal 1 bias command (torque)
*1
T110
C17
(919)
Terminal 1 bias (torque)
*1
T111
C18
(920)
Terminal 1 gain command (torque)
*1
T112
C19
(920)
Terminal 1 gain (torque)
*1
T113
241
Analog input display unit switchover
M043
*1
The parameter number in parentheses is the one for use with the LCD operation panel and the parameter unit.
 Changing the function of analog input terminal
In the initial setting, no function is assigned to terminal 1 used for analog input. To use the analog input terminal to input the
torque limit, set Pr.868 Terminal 1 function assignment to change the function. (Refer to
52
CONTROL CIRCUIT INPUT SIGNAL
Initial value
Setting range
0%
0% to 400%
0%
0% to 300%
150%
0% to 400%
100%
0% to 300%
0
0
1
Description
Set the bias torque for the terminal 1 input.
Set the converted % of the bias voltage for the
terminal 1 input.
Set the gain (maximum) torque for the terminal 1
input.
Set the converted % of the gain voltage for the
terminal 1 input.
% display
Select the unit for analog input
display.
V display
page
33.)