NOTE
• The priority of the frequency command given by the external signals is as follows: JOG operation (JOG/JOG2 signal) > stop-
on-contact control (RL/RT signal) > multi-speed operation (RL/RM/RH/REX signal) > PID control (X14 signal) > terminal 4
analog input (AU signal) > pulse train input (option FR-E8AXY) > 16-bit digital input (option FR-A8AX) > terminal 2 analog
input. Note that stop-on-contact control is disabled when PID control is enabled. When pulse train input is enabled (Pr.291 =
"1" and Pr.384 ≠ "0"), terminal 2 analog input of the inverter becomes invalid.
64
CONTROL CIRCUIT INPUT SIGNAL