 Analog input bias/gain calibration (C16 (Pr.919) to C19 (Pr.920))
• The "bias"/"gain" function can adjust the relation between the torque and the torque limit setting input signal. Examples of
setting input signals are 0 to 5 VDC or 0 to 10 VDC, and they are externally input.
• Set the bias torque of the terminal 1 input using C16 (Pr.919). (The initial value is the torque at 0 V.)
• Use C18 (Pr.920) to set the torque to the torque setting voltage set by Pr.73 Analog input selection. (The initial value is the
torque at 10 V.)
400
150
(-5V)
Bias
(-10V)
C16(Pr.919)
-100%
∗1
Calibration example of terminal 1
*1
When a negative voltage (0 to -10 V (-5 V)) is input, the torque limit value becomes "0".
• There are three methods to adjust the bias/gain torque setting voltage.
Adjustment by applying voltage between terminals 1 and 5 to set the voltage at the bias/gain torque.
page 56
Adjustment by selecting the voltage at the bias/gain torque without applying voltage between terminals 1 and 5.
page 57
Adjustment by only changing the torque without adjusting the voltage.
page 58
54
CONTROL CIRCUIT INPUT SIGNAL
Initial value
100%
0
0
5V
Torque setting signal
0
10V
C17(Pr.919)
C19(Pr.920)
-150
Gain
C18(Pr.920)