Battery Mode; Figure 5-4. Path Of Current Through The Ups In Bypass Mode - Eaton 93PM UPS Installation And Operation Manual

20–50 kw (480v four wire) – 50 kw frame
Table of Contents

Advertisement

If the UPS transfers to Bypass mode from Normal mode due to any reason other than operator intervention,
the UPS automatically attempts to transfer back to Normal mode (up to three times within a ten minute period).
The fourth transfer locks the critical load to the bypass source and requires operator intervention to transfer.
Bypass Input
Rectifier Input
Rectifier
Switchgear

Figure 5-4. Path of Current Through the UPS in Bypass Mode

5.2.5

Battery Mode

The UPS automatically transfers to Battery mode if a utility power outage occurs, or if the utility power does
not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the
inverter converts to AC power.
Figure 5-5 shows the path of electrical power through the UPS system when operating in Battery mode.
During a utility power failure, the rectifier no longer has an AC utility source from which to supply the DC output
voltage required to support the inverter. The rectifier switchgear opens and the battery instantaneously
supplies energy to the battery converter. The converter boosts the voltage so that the inverter can support the
customer's load without interruption. If bypass is common with the rectifier input, the bypass switchgear also
opens. The opening of the rectifier and bypass switchgear prevent system voltages from bleeding backwards
through the static switch and rectifier snubber components to the utility source.
If the input power fails to return or is not within the acceptance windows required for normal operation, the
battery continues discharging until a DC voltage level is reached where the inverter output can no longer
support the connected loads. When this event occurs, the UPS issues another set of audible and visual alarms
indicating SHUTDOWN IMMINENT. Unless the rectifier has a valid AC input soon, the output can be supported
for only two minutes before the output of the system shuts down. If the bypass source is available, the UPS
transfers to bypass instead of shutting down.
If at any time during the battery discharge the input power becomes available again, the rectifier and the bypass
switchgear close and the rectifier begins to supply DC current to the converter and inverter. At this point, the
unit returns to Normal mode. Depending on the total load and the duration of the battery discharge, battery
current limit alarms may be seen for a short time due to the current required to recharge the battery.
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
Bypass Switchgear
Rectifier
Switchgear
Closed
Open
Static
Switch
Inverter
Battery Converter
Battery
Switchgear
Battery
Understanding UPS Operation
Inverter
Switchgear
Main Power Flow
Trickle Current
Energized
De-Energized
www.eaton.com/powerquality
Output
5-5