Table 4-5. External Parallel CAN and Pull Chain Connections
External Parallel Terminal Block Name
Table 4-6. External Parallel CAN and Pull Chain Terminal Block Terminations
Recommended
Terminal Function
Minimum Wire Size
CAN
#18 AWG
Pull Chain
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
1
Pull Chain
2
Pull Chain Ground
3
CAN H In
4
CAN L In
5
Ground
6
Earth
7
CAN H Out
8
CAN L Out
9
Ground
10
Earth
Size of Pressure
Tightening Torque
Termination
#26–#16
0.4 (3.5) - 0.8 (7.1)
#26–#16
0.4 (3.5) - 0.8 (7.1)
Description
External parallel pull chain connections between UPSs.
External parallel CAN input connections from previous UPS.
Not Used
External parallel CAN output connections to next UPS.
Not Used
Nm (lb in)
Type Screw
Slotted
Use shielded twisted-pair wires with drain wire for
each input and return or common. Strip wire insulation
back 10 millimeters to wire terminal blocks.
Slotted
Use twisted-pair wires for each input and return or
common. Strip wire insulation back 10 millimeters to
wire terminal blocks.
UPS System Installation
Comments
www.eaton.com/powerquality
4-25