UPS System Installation
Jumper
Jumper
Thermal Sensor
Thermal Sensor Return
Figure 4-19. Thermal Sensor Terminal Assignments
Table 4-4. Thermal Sensor Connections and Wire Terminations
Terminal Name
1
Jumper
2
Jumper
3
Thermal Sensor
4
Thermal Sensor Return
Jumper
Figure 4-20. Thermal Sensor Jumper Assignments
4-22
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
Thermal Sensor
TB11
Description
Used to select battery configuration
Input: Used to signal a battery temperature out of
specification and to turn off the battery charger to
prevent thermal runaway.
Thermal
Sensor
TB11
1
2
Jumper
3
4
UPS
Internal
Batteries
Recommended
Minimum Wire Size
Twisted Pair Wires
#18 AWG Use wire
rated for 600V and
Class 1 wiring
methods.
Thermal
Sensor
TB11
1
2
Jumper
Jumper
3
4
UPS
Internal and
External
Batteries
Size of Pressure
Termination
Tightening Torque
5–7 lb in
#12-#22 AWG
(0.56–0.79 Nm)
Thermal
Sensor
TB11
1
2
3
4
UPS
External
Batteries