Eaton 93PM UPS Installation And Operation Manual page 142

20–50 kw (480v four wire) – 50 kw frame
Table of Contents

Advertisement

Product Specifications
9.2.2
UPS Output
UPS Output Capacity
Output Voltage Regulation
Output Voltage
Output Voltage Harmonic Content
Output Current
Output Voltage Balance
Output Voltage Phase
Displacement
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Load Compatibility
Overload Capability
9.2.3
UPS Environmental
Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
Agency Markings
EMI Emissions and Immunity
Electrostatic Discharge (ESD)
Immunity
9-2
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
100% rated current
± 1% (10% to 100% load)
480 Vac Wye, 4W + ground
1% maximum THD (linear load)
5% maximum THD (nonlinear load)
See Table 3-4.
< 2% for 100% maximum load imbalance (linear load)
< 2.5 for 100% maximum load imbalance (linear load)
0.1 Hz free running
± 4 Hz (default setting)
1 Hz per second (default setting)
0.8 pF Leading
0.8 pF Lagging
<110% for 10 minutes
<125% for 60 seconds
<150% for 10 seconds
>150% for 300 milliseconds
5 to 40C (41 to 104F) without derating. The recommended operating
temperature is 25C (77F).
Maximum 1500m (5000 ft) at 40C without derating
25 to +55C, excluding batteries (prolonged storage above 40C causes
rapid battery self-discharge)
95%, noncondensing
50 kW at 100% load – 65 dBA at a 1m distance, per ISO 7779
UL 924 Auxiliary Lighting and Power Equipment
Safety: UL1778 4th Ed./CSA22.2 No. 107.3 2nd Ed.
Meets IEC 62040-2 C3 and FCC Part 15 Subpart B, ICES-003, CISPR 22, VCCI:
Class A, and CISPR 24.
Meets IEC 61000-4-2 Level 3 specifications. Withstands up to 4 kV contact
pulse without damage and with no disturbance or adverse effect to the
critical load.
www.eaton.com/powerquality

Advertisement