Table 3-2. Ups Cabinet Weights; Table 3-3. Ups Cabinet Clearances - Eaton 93PM UPS Installation And Operation Manual

20–50 kw (480v four wire) – 50 kw frame
Table of Contents

Advertisement

The UPS equipment operating environment must meet the weight requirements shown in Table 3-2 and the
size requirements shown in Figure 3-1 through Figure 3-8. Dimensions are in millimeters (inches).

Table 3-2. UPS Cabinet Weights

Model
Eaton 93PM-50-1
Eaton 93PM-50-2
Eaton 93PM-50-1 with UPS Top Entry Wiring Sidecar (no breakers)
Eaton 93PM-50-2 with UPS Top Entry Wiring Sidecar (no breakers)
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are on top or in the back of the cabinet. Allow clearance in front of and on top or in
back of the cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in
Table 3-3.

Table 3-3. UPS Cabinet Clearances

From Front of Cabinet
From Top of Cabinet with Top Exhaust (Zones 1 and 3 – see Figure 3-2 ) 457.2 mm (18") minimum clearance for ventilation
From Top of Cabinet (Zones 2 and 3– see Figure 3-2 )
From Top of Cabinet with rear service access (Zone 2– see Figure 3-2) Can be less than 457.2 mm (18")
From Back of Cabinet with Rear Exhaust
From Back of Cabinet with Top Exhaust
From Back of Cabinet – Seismic Installation
From Right Side of Cabinet
From Left Side of Cabinet
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
NOTE
Refer to the Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass Installation
and Operation (50 kW and 100 kW SIAC-B) Manual, listed in paragraph 1.8, for
Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) size requirements.
UPS Installation Plan and Unpacking
Internal
Battery Strings
Frame
0
Capacity
3
Capacity
4
Capacity
0
Redundant
0
Redundant
0
Capacity
3
Capacity
4
Capacity
0
Redundant
0
Redundant
914.4 mm (36") working space
457.2 mm (18") working space
254 mm (10") minimum clearance for ventilation
None Required
914.4 mm (36") working space
None Required
None Required
www.eaton.com/powerquality
Weight
kg (lb)
Shipping
Installed
Point Loading
338 (745)
318 (702)
4 at 80 (176)
781 (1721)
761 (1678)
4 at 190 (420)
885 (1952)
865 (1909)
4 at 216 (477)
354 (780)
334 (737)
4 at 84 (184)
441 (972)
421 (929)
4 at 105 (232)
425 (937)
402 (887)
4 at 101 (222)
844 (1862)
821 (1812)
4 at 205 (453)
949 (2093)
926 (2043)
4 at 232 (511)
441 (972)
418 (922)
4 at 105 (231)
505 (1113)
482 (1063)
4 at 121 (266)