UPS System Installation
Table 4-7. Normally-Open REPO Connections and Wire Terminations
From REPO Station
Switch Contact
Block
UPS REPO
(Either Block)
Terminal
3 NO
3
4 NO
4
REPO
Switch
(NO)
NOTE
NOTE
Figure 4-26. Normally-Open REPO Switch Wiring
Table 4-8. Normally-Closed REPO Connections and Wire Terminations
From REPO Station
Switch Contact
Block
UPS REPO
(Either Block)
Terminal
3 NO
1
4 NO
2
REPO
Switch
(NC)
NOTE
NOTE
Figure 4-27. Normally-Closed REPO Switch Wiring
4-32
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
Name
Description
EPO_A
Input: Normally-open dry contact used to activate
UPS EPO from a remote switch
EPO_B
3
Twisted
Wires
4
REPO switch rating is 24 Vdc, 1A minimum.
The REPO switch must be a latching-type switch not tied to any other circuits.
Name
Description
EPO_A_B Input: Normally-closed dry contact used to activate
UPS EPO from a remote switch
GND-ISO
1
Twisted
Wires
2
REPO switch rating is 24 Vdc, 1A minimum.
The REPO switch must be a latching-type switch not tied to any other circuits.
Recommended
Minimum Wire
Size
Twisted Pair Wires
#18 AWG
1
2
REPO TB
3
4
Recommended
Minimum Wire
Size
Twisted Pair Wires
#18 AWG
1
2
REPO TB
3
4
Size of Wire
Tightening
Termination
Torque
2 lb in
#1630 AWG
(0.22-0.25 Nm)
Size of Wire
Tightening
Termination
Torque
2 lb in
#1630 AWG
(0.22-0.25 Nm)
www.eaton.com/powerquality