ESIE17-08
|
Part 5. Appendix

5.1. Field setting

5.1.1. Indoor unit

5.1.1.1. Retrieve field settings BRC1E

1.
Press and hold Cancel button for 4 seconds or more. Field setting menu is displayed.
2.
Select Field setting list in the field setting menu, and press Menu/Enter button.
Field setting list screen is displayed.
3.
Highlight the mode, and select desired "Mode No." by using ▲▼ (Up/Down) button.
4.
In the case of setting per indoor unit during group control (When Mode No. such as 20, 21, 22, 23, 25 are selected), highlight the unit No. and select "Indoor unit No." to be set by using
▲▼ (Up/Down) button. (In the case of group total setting, this operation is not needed.)
In the case of individual setting per indoor unit, current settings are displayed. And, Second Code No. "-" means no function.
5.
Highlight Second Code No. of the First Code No. to be changed, and select desired "Second Code No." by using ▲▼ (Up/Down) button. Multiple identical mode number settings are
available.
In the case of group total setting, all of Second Code No. which may be set are displayed as "*".
"*" is changed to Second Code No. to be set. And, Second Code No. "-" means no function.
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
<Basic screen>
(1)
<Field setting menu screen>
(2)
Press Menu/Enter button.
<Field setting screen>
In the case of individual
setting per indoor unit
(3)
(3)
(4)
(5)
(5)
First Code (SW) No.
Press Menu/Enter button.
<Setting confirmation screen>
(6)
(7)
Press Menu/Enter button.
<Setting confirmation>
In the case of group total
setting
Second Code No.
5.1. Field setting
Page 105