ESIE17-08
|
Part 5. Appendix

5.2.3. Remote controller

5.2.3.1. Quiet (Low Noise) Operation

Lower the operation sound of the outdoor unit.
Silent Operation can be activated by:
1.
Automatic control (by field setting from remote controller)
2.
External activation (from optional PCB KRP58M)
Quiet (Low Noise) Operation by Automatic Control
Silent operation can be set by field setting from the wired remote controller:
Description
Mode No.
Silent Operation
16(26)
Low noise start & stop time
When setting mode 16(26)-0-02, quiet (low noise) operation will be carried out by presuming the current time in accordance with the outside temperature.
Automatic mode will start when the outdoor temperature is = average max of last 10 days -5°C and will be conducted for 10 hours.
The maximum outdoor temperature is supposed to occur at 14:00h.
As the time judgement is made in accordance with the outdoor temperature, the above mentioned timing is an estimation only.
When setting mode 16(26)-0-04, the low noise operation will be stopped when the heating or cooling load increases. In that case, the operation will return to normal operation. The unit will
return to low-noise operation when the heating or cooling load decreases again.
External Activation from Optional PCB
Quiet (low noise) operation can also be activated from the optional PCB.
Quiet (low noise) operation will start when the contact on LNOP-COM is closed and will remain active as long as the contact is closed. No field setting on the outdoor unit or by remote
controller is required.
Quiet (low noise) operation will be ended when the contact is re-opened.
Use of the KRP58M enables the use of an external time clock.
Same as with the automatic control, priority for capacity can be set. Priority for capacity will be activated by changing field setting 26-0-03 in combination with the closed contact on KRP58M.
Description
Mode No.
Quiet (low noise) operation
16(26)
The Quiet (low noise) operation will be overruled in the following conditions:
Pump down residual operation
Startup control
Defrost operation
Oil recovery
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
Second Code No.
First Code No.
01
0
OFF
1
Maximum
ambient
+8 hours
temperature
Trend line indicating fluctuation of
outdoor ambient temperature in 24
hours.
Power supply connector
DS1
(on outdoor PCB X77A)
ON
OFF
1 2 3 4
X800M
3
Output on X801M = 12VDC, 12mA
Maximum wire length = 100 meter
Second Code No.
First Code No.
01
0
Factory setting
02
03
Low noise activation
22h00 ~ 06h00
End night
Start night
quiet
+10 hours
quiet
operation
operation
Transmission connector
(on outdoor PCB X6A)
X801M
2
1 LNOP COM
X801M
3
2
1 LNOP
COM
02
5.2. Detailed information setting mode
04
05
Low noise + capac-
ity priority
22h00 ~ 08h00
20h00 ~ 08h00
03
04
Capacity priority setting
Page 113