Product Specific Information; Error Codes; E9-00" - Electronic Expansion Valve Abnormality; F3-00" - Discharge Pipe Temperature Abnormality - Daikin R32 Sky-Air RZAG-M Service Manual

Table of Contents

Advertisement

ESIE17-08
|
Part 5. Appendix

5.6. Product specific information

5.6.1. Error codes

5.6.1.1. "E9-00" - Electronic expansion valve abnormality

Trigger conditions
A = 4 K
B = 10 K

5.6.1.2. "F3-00" - Discharge pipe temperature abnormality

Compressor
2YC71
2YC100

5.6.2. Component checklist

5.6.2.1. How to activate inverter test

Not available yet.
5.6.2.2. Component checklist
Component
Component name
Outdoor unit
M1C
Motor (compressor)
M1F
Motor (upper fan)
M2F
Motor (lower fan)
S1PH-A
Automatic high pressure switch
S1PH-M
Manual high pressure switch
S1PL
Low pressure switch
Y1E
Electronic expansion valve
Y3E
Electronic expansion valve
Y1S
Solenoid valve (4-way valve)
Y2S
Solenoid valve
R1T
Thermistor (air)
R2T
Thermistor (discharge)
R3T
Thermistor (suction)
R4T
Thermistor (heat exchanger inlet)
R5T
Thermistor (heat exchanger middle)
R6T
Thermistor (liquid)
Page 128
R32 Sky-Air RZAG-M
A (°C)
120
120
Connector on 71-class
X502A
X106A
X32A
X32A
X31A
X21A
X22A
X25A
X26A
X11A
X12A
X12A
X12A
X12A
X13A
B (°C)
110
110
Connector on 100/140-class
X502A
X106A
X107A
X32A
X32A
X31A
X21A
X22A
X25A
X26A
X11A
X12A
X12A
X12A
X12A
X13A
5.6. Product specific information
C (°C)
/
/
PCB
Specific
A1P
A1P
A1P
A1P
A1P
A1P
A1P
A1P
A1P
A1P
A1P
Type 1
A1P
Type 2
A1P
Type 1
A1P
Type 1
A1P
Type 1
A1P
Type 1
15/11/18
|
Version 1.1