ESIE17-08
|
Part 3. Repair
Installation
I
NFORMATION
Replace all tie wraps that were cut during removal.
1.
Proceed in reverse order.

3.3.2.5. Replacing accumulator assembly

Not applicable.

3.3.2.6. Replacing compressor

PRELIMINARY ACTIONS
1.
Switch off the Daikin unit via the user interface.
2.
Switch off the Daikin unit with the field supplied circuit breaker.
3.
Remove plate work when required (refer to
4.
Recover the refrigerant (refer to
5.
Remove the compressor jacket.
6.
Remove the lower propeller fan (refer to
7.
Connect a nitrogen hose to the outdoor suction service port.
8.
Attach a hose with core-depressor to allow the release of the nitrogen.
PROCEDURE
Removal
1.
Cut the 2 tie wraps that fix the power and communication wires to the stop valve mounting plate.
2.
Loosen and remove the 4 screws (1) that fix the stop valves.
C
AUTION
The 2 screws that are removed in the next step must be re-installed in the same location upon reassembly.
3.
Loosen and remove the 2 screws (2) that fix the stop valve mounting plate (3).
4.
Lift and remove the stop valve mounting plate (3).
15/11/18
|
Version 1.1
R32 Sky-Air RZAG-M
"Basic removal" on page
"Refrigerant repair procedures" on page
"Replacing propeller fan blade assembly" on page
3.3. Unit specific repair procedures
67).
61).
99).